Specifications: | Overall dimension(mm) | Install dimension(mm) | Drawing | ||||||||
W1 | H1 | D | W2 | H2 | d | ||||||
7.5KW-45KW | 145 | 315 | 215 | 85 | 298 | M8 | 1 | ||||
55KW-90KW | 210 | 360 | 255 | 150 | 343 | M8 | 2 | ||||
115KW-160KW | 330 | 465 | 255 | 260 | 440 | M8 | 2 | ||||
115KW-160KW | 490 | 652 | 295 | 335 | 535 | M8 | 2 | ||||
320KW-630KW | 680 | 840 | 420 | 350 | 780 | M10 | 2 | ||||
Model | Voltage (V) | Power (KW) | Current (A) |
18.5-Z | 380 | 18.5 | 37 |
22-Z | 380 | 22 | 45 |
30-Z | 380 | 30 | 60 |
37-Z | 380 | 37 | 75 |
45-Z | 380 | 45 | 90 |
55-Z | 380 | 55 | 110 |
75-Z | 380 | 75 | 150 |
90-Z | 380 | 90 | 180 |
115-Z | 380 | 115 | 230 |
132-Z | 380 | 132 | 260 |
160-Z | 380 | 160 | 320 |
185-Z | 380 | 185 | 370 |
200-Z | 380 | 200 | 400 |
220-Z | 380 | 220 | 450 |
250-Z | 380 | 250 | 500 |
280-Z | 380 | 280 | 560 |
320-Z | 380 | 320 | 630 |
355-Z | 380 | 355 | 710 |
400-Z | 380 | 400 | 800 |
450-Z | 380 | 450 | 900 |
500-Z | 380 | 500 | 1000 |
600-Z | 380 | 600 | 1200 |
Input Power Supply: | Input Voltage:Three-phase 380V/480V/660V/690V AC. Frequency:50/60Hz . Adaptive Motor:Squirrel-cage three-phase asynchronous motor. Starting Times:It is recommended not to exceed 20 times per hour. | ||||||
Control Mode: | (1)Operation panel control. (2)Operation panel + external control. (3)External control. (4)External control + COM control. (5)Operation panel + external + COM control. (6)Operation panel + COM control. (7)COM control. (8)No start or stop operation. | ||||||
Start Mode: | (1) Current-limiting to start. (2) Voltage tamp to start. (3) Torque control + current-limiting to start. (4) Torque control + voltage ramp to start. (5) Current ramp to start. (6) Voltage current- limiting double closed-loop start. | ||||||
Stop Mode: | (1) Soft stop. (2) Free stop. | ||||||
Protective Function: | (1) Open loop protection for soft starter. (2) Over-heat protection for soft starter. (3) Protection for too long starting time. (4) Input open phase protection. (5) Output open phase protection. (6) Unbalanced three -phase protection. (7) starting over current protection. (8) Running overload protection. (9) Under voltage protection for power voltage. (10) Over voltage protection for power voltage. (11) Protection for fault setting. (12) Load short circuit protection. (13) Auto restart or incorrect wiring protection. (14) Incorrect wiring protection of external control stop terminals. | ||||||
Ambient: | Place to be used: Indoor location with good ventilation free from corrosive gas and conductive dust. Altitude: Below 1000M.It have to rise the rate pwoer when the altitude is more then 1000M. Temperature: -20 +45°C Humidity: 90%RH without dew condensation. | ||||||
Structure: | protection Class: IP20. Cooling Pattern: Fans cooling. | ||||||





Low Price and Characteristic 2 Years Warranty 3phase 50hz 60hz 37 kw Soft Starter 380V/660V for AC Motor Soft Starter
Factory Direct Sales Quality Assurance Ac Motor 400A 380V 50Hz/60Hz China Bypass Soft Starter 200 kw 400kw 630kw 3 Phase
SHCKELE Soft Starter 180A Online 90KW 125HP 3 Phase AC Asynchronous Motor for Water Supply Pump/conveyer Voltage Ramp Control
China Suppliers Three Phase 380v 280w 50hz/60hz Ac Motor Soft Starter for Ac Motor Soft Starter Panel
Open Loop Protection 380V 75KW 100HP Bypass Soft Starter for AC 3 Phase Motor 110A Contactors for Air Compressor
SHCKELE Manufacturer's 5.5KW 380V Triple Phase Soft Starter for 7.5HP Asynchronous AC Motor for Circulating Pumps Conveyer